1
2023 NEC Changes
Important: Please refer to the 2023 National Electrical Code for detailed information
Revised August 28, 2024
1. Section 110.26: The requirement for “large equipment” from 110.26(C)(2) which stated that
open equipment doors may not impede access to and egress from the working space was also
added to 110.26. This rule now requires that when open equipment doors result in an egress
path that is less than 24 inches wide or 6 feet, 6 inches high, the opening must be increased to
prevent the equipment doors from obstructing the egress path. In addition, the language
clarifies that the space in front of equipment must be unobstructed by fixed cabinets, walls, or
partitions.
2. Section 110.26(A)(4): Since the 2014 NEC, the NEC has required working clearances and
opening dimensions for safe access to electrical equipment in spaces with limited access. In
the 2023 NEC, language was added to (4) to address the workspace area for safely servicing
electrical equipment with limited access. The new requirement will not allow for the
placement of fixed cabinets, walls, or partitions below the limited access opening. The space
below the opening is required to be unobstructed to the floor and free from any obstacles
that may hinder equipment access.
3. Section 210.8(A)(6): GFCI protection requirements in dwelling unit kitchens has been
expanded. The revised language in the 2023 NEC removed the phrasewhere the receptacles
are installed to serve the countertop surfaces, thereby expanding the GFCI protection
requirement to include any 125-volt through 250-volt receptacle in kitchens not just on
countertop surface. Now the NEC will require GFCI protection for all kitchen receptacles;
including the wall space receptacles required by 210.52(A), and the kitchen countertop
surfaces covered in 210.52(B).
4. Sections 210.8(A)(7) and 210.8(B)(3): The revised language will require GFCI protection for
receptacles located in “areas with sinks and permanent provisions for food preparation,
beverage preparation, or cooking”. These areas are used similarly to a kitchen, but do not
meet the definition. The change could affect an area that includes a sink such as a recreation
room wet-bar, or a convenience store where beverages or food is prepared. For the purposes
of determining the area where receptacle(s) are required to have GFCI protection, the area
includes the contiguous countertop or work surface that contains the sink.
2
5. Section 210.8(B)(4): For the 2023 NEC, GFCI protection will be required for other than
dwelling unit” receptacles in buffet serving areas. The intent of the language was to include
serving areas where you have either permanent provisions for food serving, beverage serving,
or cooking. The department will enforce the GFCI protection requirements for receptacles
located in areas of buildings where liquids or beverages are present or dispensed. The
intended areas may include but are not limited to buffet tables or buffet areas which contain
water wells used for heating food, smoothie bars, juice bars, coffee bars, and soda dispensing.
GFCI protection will not be required for appliances located in buffet areas that do not contain,
dispense, or use liquids (beverages or water) and are used exclusively for warming and heating
food. Those heating appliances may include pizza warmers, hot dog rollers/cookers, heat
lamps, etc.
6. Section 210.8(D): A list of “specific appliances was added that will require GFCI protection for
the branch-circuit or theoutlet” supplying appliances rated 150V or less to ground and 60A
or less. The section clarifies that these appliances must have GFCI protection provided
whether they are hardwired, or cord- and plug-connected. The expansion also included 5 new
appliances:
o Electric range
o Wall-mounted oven
o Counter-mounted cooking unit
o Clothes dryer
o Microwave oven
7. Section 210.8 (F): A new exception was added to not require GFCI protection for listed HVAC
equipment until September 1, 2026. Garages, accessory buildings, and boathouses were
added to dwelling unit outdoor outlets and will require GFCI protection. In addition, GFCI
protection must be added for existing outdoor equipment that is replaced.
210.8(F) is not applicable to:
Outdoor outlets that are not readily accessible such as a submersible well pumps, sewer
lift pumps, load management controllers, surge protection devices, or similar equipment.
Outdoor lighting outlets
8. Section 210.52(C)(2): The requirement for receptacles serving the countertop or work surface
of an island or peninsula is made optional; however, if the receptacles are not installed at the
time the cabinets and countertops were initially placed, the section requires provisions for a
future outlet to be provided. The provision must include a wiring method (conduit, raceway,
or cable) to be extended to the island or peninsula and terminated into a junction box with
cover.
3
9. Section 210.52(C)(3): In the same section, all receptacle outlets in the kitchen serving the
countertop surface will no longer be allowed below the countertop or work surface. The
receptacles, or outlet assemblies, located on the top of the countertop or work surface must
be listed for the use.
For purposes of this section, receptacles shall not be located within 24 inches below a
countertop or worksurface. Receptacles below the countertop or worksurface shall not be
used for serving the countertop or worksurface.
USB device(s) that do not contain a
receptacle(s) are allowed to be installed below the countertop surface.
**If receptacle placement is according to Informational Annex J and with ADA guidelines,
please contact the local AHJ to discuss options for granting “special permission” in accordance
with section 90.4(C).
10. Section 210.70(A)(1): Laundry areas were added to the list of rooms that are required to have
at least one lighting outlet controlled by listed wall mounted control device when you enter
the room. In addition, exception number one (1) was revised to clarify that the laundry area
could not utilize a switched receptacle for the lighting outlet. The lighting outlet and switch
requirement would not apply to laundry rooms or areas that are in small closets or rooms only
large enough for the laundry equipment, if the light source located in the adjacent space
provides illumination.
11. Section 215.15: A new section was added to expand the barrier requirement for feeder taps
and transformer secondaries. Barriers shall be placed such that no energized, uninsulated,
ungrounded busbar or terminal is exposed to inadvertent contact by persons while servicing
load terminations in panelboards, switchboards, switchgear, or motor control centers supplied
by feeder taps in 240.21(B), or transformer secondary conductors in 240.21(C), when the
disconnecting device, to which the tap conductors are terminated, is in the open position.
12. Sections 215.18, 225.42 and 230.67: New language was added similar to section 230.67 to
require surge protection devices (SPDs) for both feeders and outside feeders. The need for the
protection is to limit damage to electronic devices and equipment which can be rendered
inoperable by a surge. The areas where the surge protection is required has been expanded
and will now include new installations as well as replacement distribution equipment located
in:
(1) Dwelling units
(2) Dormitory units
(3) Guest rooms and guest suites of hotels and motels
(4) Areas of nursing homes and limited-care facilities used exclusively as patient sleeping
rooms
The Type 1 or Type 2 SPD must be installed in or adjacent to the distribution equipment
4
connected to the load side of the feeder that contains branch circuit overcurrent protective
device(s). This requirement does not apply to a feeder disconnect that supplies a single branch
circuit. In addition, the SPD shall have a nominal discharge current rating (In) of not less than
10kA.
13. Section 225.41: New language now requires a one- and two-family dwelling unit “emergency
disconnect” for outside feeders. This requirement was first introduced in section 230.85 in the
2020 NEC for services. The need for the change was to ensure that first responders were
always able to shut off the power on the exterior of a dwelling regardless of how the building
is supplied.
An emergency disconnect covered in section 225.41 would not be required when replacing a
panelboard supplied by an existing outside feeder.
In addition, section 225.41(B) requires the identification of the location of other isolation
disconnects for other power sources where those disconnects are not located adjacent to the
emergency disconnect. For purposes of applying the emergency disconnect requirements in
225.41 and 230.85, the Department will allow an exterior utility provided disconnect as the
emergency disconnect if the following conditions are met: the disconnect is located outdoors,
readily accessible, and visible from the dwelling it supplies.
14. Section 230.85: In order to provide first responders with a safe method of disconnecting
power from a structure, one-family and two-family dwellings are required to have an
emergency disconnect installed outdoors, within sight, and in a readily accessible location.
The emergency disconnect must be rated for the available fault current. Generally, to achieve
a short circuit current rating, an unfused disconnect switch constructed to UL 98, would be
required to contain overcurrent protection or the installer must provide the overcurrent
protection ahead of or adjacent to the equipment. In addition, this requirement will impact
service panels that are being replaced. If you have questions regarding the limitations and use
of an unfused disconnect - please contact the local AHJ.
See 230.85(E) for the equipment marking requirements. The NEC does not prohibit locking the
disconnect in theOn” position. First responders are well equipped to cut off or remove any
locking devices that impede the ability to operate the emergency disconnect.
For the purposes of applying the exception,replacement” is installing new meter enclosures,
terminal boxes, raceways, or service entrance cables (including overhead to underground), to
existing electrical installations without changing the service panelboard.
15. Section 250.140(B)(5): For existing branch-circuit installations only, if an equipment grounding
conductor is not present in the outlet or junction box the frame of the range or dryer shall be
permitted to be connected to the grounded conductor that is part of a Type SE service-
entrance cable that originates in equipment other than a service. The grounded conductor
5
shall be insulated, or field covered within the supply enclosure with listed insulating material,
such as tape or sleeving to prevent contact of the uninsulated conductor with any normally
non-current-carrying metal parts. Note: Prior editions of the NEC only allowed the existing
branch-circuit installation to use the grounded conductors as the equipment ground if it
originated in a service panelboard.
16. Section 352.44(B): A new (B) was added to address earth movement when installing
underground PVC conduit. Expansion fittings are now required to compensate for earth
settling or movement, including frost heaving, when underground PVC conduit is installed as a
complete run (300.18(A)), and emerges from grade. Short sections of PVC conduit installed for
physical protection of direct buried cables shall comply with requirements in 300.5(J).
17. Section 406.9: The 2020 NEC addressed receptacles prohibited from being installed inside a
tub or shower or within a zone measured 3 feet horizontally from any outside edge and 8’
vertically above the top of the bathtub rim or shower stall threshold. In the 2023 NEC, the
language was changed to clearly include the space from the floor to 8 ft above the bathtub or
shower threshold. In addition, some new exceptions were added. Exception No.
1: Receptacles installed in accordance with
680.73 (receptacles for hydromassage bathtubs)
are allowed. Exception No. 4: to allow a single receptacle for an electronic toilet or personal
hygiene device such as an electronic bidet seat. The receptacle is required to be readily
accessible and not located in the space between the toilet and the bathtub or shower.
18. Section 440.14: The revised text clarifies that the required air-conditioning and refrigeration
equipment disconnecting means located within sight from and readily accessible, shall meet
the working space requirements of 110.26(A).
19. Section 445.19(C): New language clarified that an “Emergency Shutdown of Prime Mover
shall be provided for one -and- two-family dwelling unit generators. For other than cord-and-
plug-connected portable generators, an emergency shutdown device shall be located outside
the dwelling unit at a readily accessible location and shall also meet the requirements of
445.19(A)(1) and (A)(2).
An emergency shutdown device mounted on the exterior of the generator enclosure shall be
permitted to satisfy the requirements of this section. The shutdown device shall be marked as
the Generator Emergency Shutdown, and the label shall meet the requirements of 110.21(B).
20. Section 725.31: This section was revised, and the acceptable wiring methods were relocated
to section 724.31. This section covers the additional protection requirements for a safety
control circuit where failure or damage would introduce a direct fire or life hazard. “Safety
Circuit” is defined in the 2023 NEC asthe part of a control system containing one or more
devices that perform a safety-related function.” It is the department’s position that inverters,
ESS, and other related systems, that use power limited signal circuits to activate an external
emergency switch or disconnect be considered safety circuits. All conductors shall be installed
6
in rigid metal conduit, intermediate metal conduit, rigid nonmetallic conduit, electrical
metallic tubing, Type MI cable, or Type MC cable, or be otherwise suitably protected from
physical damage.