shall be insulated, or field covered within the supply enclosure with listed insulating material,
such as tape or sleeving to prevent contact of the uninsulated conductor with any normally
non-current-carrying metal parts. Note: Prior editions of the NEC only allowed the existing
branch-circuit installation to use the grounded conductors as the equipment ground if it
originated in a service panelboard.
16. Section 352.44(B): A new (B) was added to address earth movement when installing
underground PVC conduit. Expansion fittings are now required to compensate for earth
settling or movement, including frost heaving, when underground PVC conduit is installed as a
complete run (300.18(A)), and emerges from grade. Short sections of PVC conduit installed for
physical protection of direct buried cables shall comply with requirements in 300.5(J).
17. Section 406.9: The 2020 NEC addressed receptacles prohibited from being installed inside a
tub or shower or within a zone measured 3 feet horizontally from any outside edge and 8’
vertically above the top of the bathtub rim or shower stall threshold. In the 2023 NEC, the
language was changed to clearly include the space from the floor to 8 ft above the bathtub or
shower threshold. In addition, some new exceptions were added. Exception No.
1: Receptacles installed in accordance with
680.73 (receptacles for hydromassage bathtubs)
are allowed. Exception No. 4: to allow a single receptacle for an electronic toilet or personal
hygiene device such as an electronic bidet seat. The receptacle is required to be readily
accessible and not located in the space between the toilet and the bathtub or shower.
18. Section 440.14: The revised text clarifies that the required air-conditioning and refrigeration
equipment disconnecting means located within sight from and readily accessible, shall meet
the working space requirements of 110.26(A).
19. Section 445.19(C): New language clarified that an “Emergency Shutdown of Prime Mover”
shall be provided for one -and- two-family dwelling unit generators. For other than cord-and-
plug-connected portable generators, an emergency shutdown device shall be located outside
the dwelling unit at a readily accessible location and shall also meet the requirements of
445.19(A)(1) and (A)(2).
An emergency shutdown device mounted on the exterior of the generator enclosure shall be
permitted to satisfy the requirements of this section. The shutdown device shall be marked as
the Generator Emergency Shutdown, and the label shall meet the requirements of 110.21(B).
20. Section 725.31: This section was revised, and the acceptable wiring methods were relocated
to section 724.31. This section covers the additional protection requirements for a safety
control circuit where failure or damage would introduce a direct fire or life hazard. “Safety
Circuit” is defined in the 2023 NEC as “the part of a control system containing one or more
devices that perform a safety-related function.” It is the department’s position that inverters,
ESS, and other related systems, that use power limited signal circuits to activate an external
emergency switch or disconnect be considered safety circuits. All conductors shall be installed